📖 Vapour absorption: a fridge driven by heat
An absorption fridge keeps the condenser, expansion valve and evaporator of a normal fridge, but the compressor is replaced by an absorber, a small pump and a generator. Water soaks up the ammonia vapour; heat (a flame, steam or waste heat) drives it back out at high pressure.
- Evaporator: liquid ammonia boils at low pressure, taking heat Q_E from the cold space.
- Absorber: water soaks up the vapour (strong solution) and gives off heat Q_A, so it is cooled.
- Pump: lifts the liquid solution to the high pressure: very small work W_p.
- Generator heat Q_G drives the ammonia out; the rectifier dries it; a heat exchanger saves heat.
- COP = Q_E / (Q_G + W_p); the unit balances: Q_G + W_p + Q_E = Q_A + Q_C.
- COP_max = [(T_G − T_0)/T_G] × [T_E/(T_0 − T_E)]: an ideal engine driving an ideal fridge.
More detail (for the exam) ▾
COP = Q_E / (Q_G + W_p) · Q_G + W_p + Q_E = Q_A + Q_C
COP_max = [(T_G − T_0) / T_G] × [T_E / (T_0 − T_E)]
📝 Exam note: write it like this
The cycle: ammonia (refrigerant) and water (absorbent). Low-pressure NH₃ vapour from the evaporator is absorbed in weak aqua-ammonia in the absorber (cooled by water, as absorption releases heat). The strong solution is pumped through the heat exchanger to the generator, where heat boils NH₃ vapour out. The analyser and rectifier remove the water vapour, so dry NH₃ goes to the condenser, expansion valve and evaporator. The hot weak solution returns through the heat exchanger and a pressure-reducing valve to the absorber.
Maximum COP: the generator gets Q_G at T_G, the absorber and condenser reject heat at T_0, the evaporator takes Q_E at T_E. Treat it as a reversible engine (T_G → T_0) whose work W = Q_G (T_G − T_0)/T_G drives a reversible fridge (T_0 → T_E) with Q_E = W T_E/(T_0 − T_E). So Q_E/Q_G = [(T_G − T_0)/T_G] × [T_E/(T_0 − T_E)].
Compared with vapour compression: runs on low-grade heat instead of shaft work; the only moving part is a small pump, so it is quiet with little wear; capacity is easy to control with the heat supplied; but its COP is lower and the plant is bulkier.
Maximum COP: the generator gets Q_G at T_G, the absorber and condenser reject heat at T_0, the evaporator takes Q_E at T_E. Treat it as a reversible engine (T_G → T_0) whose work W = Q_G (T_G − T_0)/T_G drives a reversible fridge (T_0 → T_E) with Q_E = W T_E/(T_0 − T_E). So Q_E/Q_G = [(T_G − T_0)/T_G] × [T_E/(T_0 − T_E)].
Compared with vapour compression: runs on low-grade heat instead of shaft work; the only moving part is a small pump, so it is quiet with little wear; capacity is easy to control with the heat supplied; but its COP is lower and the plant is bulkier.
⚠️ Common mistakes
- Taking COP = Q_E / W_p: the generator heat Q_G is the main input, so COP = Q_E / (Q_G + W_p).
- Using °C in COP_max: all three temperatures must be in kelvin.
- Forgetting the absorber gives off heat: Q_A leaves to the cooling water along with Q_C.
- Thinking the pump does the compressor's work: it only lifts a liquid; the generator's heat does the rest.
All cases and numbers are our own. Ammonia saturation pressures and enthalpies: NIST Chemistry WebBook (SRD 69, ammonia reference equation of state).