📖 The Bell–Coleman air refrigeration cycle
Run a gas turbine backwards and you get a fridge. Air is squeezed (it gets hot), cooled back near room temperature, then expanded in an expander that does work, so it gets very cold. That icy air takes heat from the cold room. This is the Bell–Coleman (reversed Brayton) cycle.
- Four parts: compressor, cooler, expander, cold room; one shaft links compressor and expander.
- 1→2 and 3→4 are isentropic (ideally); 2→3 and 4→1 are at constant pressure.
- Refrigerating effect q_R = cp (T1 − T4); net work w = cp(T2 − T1) − cp(T3 − T4).
- COP = q_R / w = 1 / (r_p^((γ−1)/γ) − 1) for ideal machines.
- Lower pressure ratio → higher COP, but less cold per kg, so more air is needed.
- Real machines (η_c, η_e < 1) raise T2 and T4: the COP falls a lot. Used in aircraft: air is light and safe.
More detail (for the exam) ▾
T2 = T1 r_p^((γ−1)/γ) · T4 = T3 / r_p^((γ−1)/γ)
q_R = cp (T1 − T4) · q_rej = cp (T2 − T3) · w = q_rej − q_R
COP = (T1 − T4) / [(T2 − T3) − (T1 − T4)] = 1 / (r_p^((γ−1)/γ) − 1)
Real: T2′ = T1 + (T2 − T1)/η_c · T4′ = T3 − η_e (T3 − T4)
📝 Exam note: write it like this
Performance: COP = refrigerating effect / net work. It depends only on the pressure ratio for ideal machines and is low compared with vapour compression, because heat is taken in and given out over a range of temperatures, not at constant temperature. Air refrigeration is used for aircraft cabin cooling because the equipment is light and the air is safe and freely available.
⚠️ Common mistakes
- Using cv instead of cp: the heat exchanges are at constant pressure.
- Forgetting the expander's work: net work = compressor work − expander work.
- Taking T4 = cold-room temperature: T4 is the (much colder) air leaving the expander.
- Applying η_e the wrong way round: T4′ = T3 − η_e (T3 − T4s), so a poor expander gives warmer air.
Physics from our own tested model (air as a perfect gas, cp = 1005 J/kg·K, γ ≈ 1.4). All numbers and examples are our own.