📖 The vapour compression cycle: how a fridge moves heat
A fridge pumps heat uphill: from the cold food to the warm kitchen. A liquid refrigerant (R-134a) boils in the evaporator inside, taking heat; the compressor squeezes the vapour; it gives the heat to the room in the condenser at the back; the capillary tube drops the pressure so it is cold again.
- 1→2 compressor: isentropic compression, s₂ = s₁, work w = h₂ − h₁.
- 2→3 condenser: heat to the room at constant pressure, q_c = h₂ − h₃.
- 3→4 expansion (throttling): h₄ = h₃; liquid flashes to a cold wet mix.
- 4→1 evaporator: refrigerating effect q = h₁ − h₄ from the food.
- COP = q / w; capacity in TR: 1 TR = 211 kJ/min = 3.517 kW.
- Refrigeration tables give h and s: hg, sg at T_e; hf at T_c; superheat table for 2.
More detail (for the exam) ▾
q = h₁ − h₄ · w = h₂ − h₁ · q_c = h₂ − h₃ = q + w · h₄ = h₃
COP = (h₁ − h₄) / (h₂ − h₁) · ṁ = capacity / q · COP_Carnot = T_e / (T_c − T_e)
📝 Exam note: write it like this
Performance: the COP falls when the evaporator temperature is lowered or the condenser temperature is raised (bigger pressure ratio, more work, less refrigerating effect). Example at −10 °C / 40 °C (our own, R-134a): q = 136.3 kJ/kg, w = 33.8 kJ/kg, COP = 4.03.
⚠️ Common mistakes
- Taking h₄ from the evaporator table: h₄ = h₃ (hf at the CONDENSER temperature).
- Using hg at the condenser for h₂: state 2 is superheated; read it at P_c with s₂ = s₁.
- Writing COP = q_c / w: that is the heat pump COP (it is one more than the fridge COP).
- Mixing tables with different reference states: h values differ, but every difference (and so COP) is the same.
Fridge settings and examples are our own. R-134a properties from our own implementation of the Tillner-Roth & Baehr (1994) equation of state (IIR reference: h = 200 kJ/kg, s = 1 kJ/kg·K for saturated liquid at 0 °C), checked against NIST WebBook values.