📖 Adiabatic saturation and the psychrometric chart
Blow air through a long insulated duct over water. Water evaporates into it and takes its latent heat from the air, so the air cools and gets wetter until it leaves saturated. That exit temperature is the thermodynamic wet bulb temperature t*: a property of the air going in.
- Adiabatic saturation: no heat, no work; make-up water enters at t*.
- Energy per kg dry air: h₁ + (ω₂ − ω₁) h_f* = h₂, with ω₂ = ω_s(t*).
- Carrier's equation: p_v = p_w − (P − p_w)(t_db − t_wb)/(1544 − 1.44 t_wb).
- For air–water, a sling's wet bulb ≈ the thermodynamic wet bulb.
- Psychrometric chart: DBT across, ω up; curves of constant φ, wet bulb and h.
- The wet duct runs up a line of constant wet bulb, to the saturation curve.
More detail (for the exam) ▾
ω₁ = [c_pa (t* − t₁) + ω₂ h_fg*] / (h_g1 − h_f*) · ω₂ = 0.622 p_sat(t*) / (P − p_sat(t*))
Carrier: p_v = p_w − (P − p_w)(t_db − t_wb) / (1544 − 1.44 t_wb), p_w = p_sat(t_wb), t in °C · h = 1.005 t + ω (2500 + 1.88 t)
📝 Exam note: write it like this
Thermodynamic wet bulb temperature: the temperature at which air, by evaporating water into it adiabatically, reaches saturation, the water being supplied at that same temperature. It depends only on the state of the air going in.
Carrier's equation (as in R.K. Rajput, P.K. Nag) gives the vapour pressure from psychrometer readings; then φ, ω, dew point follow.
Psychrometric chart (at 1.01325 bar): DBT on the base, ω (and dew point) on the side, saturation curve on the left; lines of constant φ, WBT, h and specific volume.
Carrier's equation (as in R.K. Rajput, P.K. Nag) gives the vapour pressure from psychrometer readings; then φ, ω, dew point follow.
Psychrometric chart (at 1.01325 bar): DBT on the base, ω (and dew point) on the side, saturation curve on the left; lines of constant φ, WBT, h and specific volume.
⚠️ Common mistakes
- Taking t* as the dew point: the air gains vapour on the way, so t* sits between the dew point and the dry bulb.
- Using p_sat at the DRY bulb as p_w in Carrier's equation: p_w is p_sat at the WET bulb.
- Thinking the duct needs heat: it is adiabatic; the latent heat comes from the air itself.
- Reading ω on a slanted line: ω (and dew point) lines are horizontal.
Air states and numbers are our own, from our tested psychrometry (steam tables for p_sat, h_f, h_g).